Refrigerant Fault Diagnosis

Enter suction pressure, discharge pressure, superheat, and subcooling readings to diagnose overcharge, undercharge, or other refrigerant system faults. Covers R-410A, R-32, R-22, and R-454B.

⚠️ Note: Refrigerant handling requires licensed certification in Canada. This tool interprets readings for diagnostic understanding; adding or recovering refrigerant must be performed by a certified technician.
°F
PSIG
°F
°F
PSIG
°F
°F
📀 Refrigerant Diagnosis Results
Superheat
LowTargetHigh
Subcooling
LowTargetHigh

Reading Summary

ReadingValueTargetStatus
Export:

How to Use the Refrigerant Fault Diagnosis Tool

Enter your system's metering device type first, since this determines which measurement (superheat or subcooling) is the more reliable charge indicator. Then enter both suction-side and liquid-side readings for a complete cross-check.

1
Why Metering Device Type Changes the Analysis

On fixed-orifice systems, superheat is the primary charge verification measurement, since the orifice doesn't adjust for charge level. On TXV systems, the valve actively maintains target superheat, making subcooling the more reliable charge indicator instead. This tool weighs your readings accordingly based on your selected metering device type.

2
Cross-Referencing With Airflow

Low airflow can produce readings that mimic low refrigerant charge, so before concluding a charge issue exists, confirm airflow is adequate using the airflow diagnosis calculator. For coil-icing-specific analysis using these same readings, see the evaporator freeze calculator.

Superheat and Subcooling: The Foundation of Refrigerant Diagnosis

Superheat and subcooling are the two fundamental measurements technicians use to verify refrigerant charge and diagnose a wide range of system faults. Understanding what each measurement represents physically, and why the correct choice between them depends on metering device type, is essential background for interpreting field readings correctly.

What Superheat Measures

Superheat is the temperature of refrigerant vapour above its saturation temperature at the measured pressure -- in practical terms, how much additional heat the vapour has absorbed after fully evaporating from liquid to gas inside the evaporator coil. It's calculated as: measured suction line temperature minus saturated evaporating temperature (derived from suction pressure using refrigerant-specific pressure-temperature relationships). Some superheat is necessary to ensure only vapour, not liquid, returns to the compressor, protecting it from the mechanical damage that liquid refrigerant slugging can cause.

What Subcooling Measures

Subcooling is the temperature of liquid refrigerant below its saturation temperature at the measured pressure -- how much additional cooling occurred to the refrigerant after it fully condensed from gas back to liquid inside the condenser coil. It's calculated as: saturated condensing temperature (derived from liquid line pressure) minus measured liquid line temperature. Adequate subcooling ensures fully liquid refrigerant (not a liquid-vapour mixture) reaches the metering device, which is necessary for the device to meter flow accurately.

Why Metering Device Type Determines Which Measurement Matters More

Fixed-orifice metering devices (including simple orifices and capillary tubes) have a fixed physical opening size that doesn't respond to changing system conditions. As refrigerant charge increases or decreases, the pressure drop and flow characteristics through this fixed opening change, which directly affects the superheat produced at the evaporator outlet -- making superheat a reliable, direct indicator of charge level on these systems. TXV (thermostatic expansion valve) systems work differently: the valve actively modulates its opening based on a sensed bulb temperature at the evaporator outlet, specifically to maintain a consistent target superheat regardless of moderate charge variations. This is precisely why superheat becomes an unreliable charge indicator on TXV systems -- the valve is designed to compensate and hold superheat roughly constant even as charge varies within its working range, masking charge problems that would otherwise show up in the superheat reading. Subcooling, measured at the condenser rather than the evaporator, isn't subject to this TXV compensation and remains a reliable charge indicator on these systems.

Reading Both Measurements Together for Confidence

While metering device type determines which single measurement is theoretically more reliable, checking both superheat and subcooling together, and confirming they point in a consistent direction, significantly increases diagnostic confidence regardless of metering device type. Undercharge classically shows high superheat combined with low subcooling -- both readings independently suggesting insufficient refrigerant mass in the system. Overcharge shows the inverse: low superheat combined with high subcooling. When both readings agree, the diagnosis is more certain; when they conflict, this often points toward a different underlying issue (airflow restriction, non-condensable gases, a restricted metering device or filter drier) rather than a straightforward charge problem, warranting more careful investigation with the condenser performance check and compressor diagnosis tool.

Frequently Asked Questions

Superheat, measured at the suction line, is the primary charge-verification method for fixed-orifice systems, since these don't self-adjust for charge level. Subcooling, measured at the liquid line, is primary for TXV systems, since a TXV actively maintains target superheat regardless of charge level within a working range, making superheat unreliable for charge diagnosis on TXV systems while subcooling remains reliable.

Fixed-orifice systems: target superheat typically 8-12°F under standard conditions, though exact target varies with indoor/outdoor conditions and should be checked against a manufacturer superheat chart. TXV systems: target subcooling typically 10-15°F, per manufacturer specification for that model. Always check manufacturer literature for the specific equipment when precision matters.

A classic signature of low refrigerant charge (undercharge). Insufficient refrigerant means the evaporator doesn't have enough liquid to fully utilize its coil surface, causing early evaporation and further superheating (high superheat). Simultaneously, the condenser has less refrigerant mass, resulting in less subcooled liquid before the liquid line (low subcooling). Both readings agreeing increases confidence in the undercharge diagnosis.

Typically indicates refrigerant overcharge. Excess refrigerant floods more of the evaporator with liquid, leaving less surface for vapour superheating (low superheat), while backing up in the condenser and increasing subcooled liquid volume (high subcooling). A licensed technician should always confirm before removing refrigerant, since removal requires proper recovery equipment and procedures under Canadian regulations.